|
UNDERSTANDING THE
HUMIDISTAT AND HOW THEY WORK AND WHERE TO INSTALL THEM
The difference between the 2
controllers is the conditions that they shut off. The HUB (damp weather shut
off) is recommended to be set at 75% RH. The operation of it will cause it
to shut down at any RH above the set point. The HUC is the opposite, it will
turn on at any condition above the set point. Operation is such that the 2
controllers when plugged together in series will maintain the humidity in
the crawl space between the set points on the controllers. For example, the
HUB set at 75% and the HUC set at 50% will run at anytime the crawl space
has a humidity below 75% and above 50%. If the humidity drops below 50% the
HUC will shut off and the fan will no longer run. If the humidity in the
space goes above 75% the HUB will shut off and the fan will no longer run.
The HUB is intended to be placed in the airstream of the incoming outside
air, therefore, if it is raining or humid out and the fan comes on and
starts bringing in air above the HUB setpoint (75%), the HUB will turn off
and the fan will stop. The obvious down side to this is that if the crawl
space rises above the setpoint of the HUB, the fan will not turn on.
However, without the HUB, the HUC would turn on at anytime the crawlspace
was above its setpoint and run the fan, it could very well bring in more
humid air than is already in the crawlspace, such as when it was raining
outside.
There are several theories regarding moisture
control in the crawlspace. We utilize the theory that moving air will dry
moisture. That basically answers questions by homeowners, but let's not
leave it there!
The powered system is designed the way we
like to see them. Ideally we would like to see all of the powered units
connected to 1 Humidistat C. This unit should be placed near the center of
the crawlspace. This does what the homeowner needs and turns the fans on
when the humidity reaches an undesirable level (50% rh). A Humidistat B,
also called Damp Weather Shut Off needs to be placed approximately 3 feet
behind a vent on the opposite side of the crawlspace from the powered vents.
This unit is set at 75%, and the Humidistat C is connected to it. This takes
away the opportunity for humid air to enter. If the outside air is above the
setting, the units will not come on, or, if they are running and it starts
to rain the units will shut off.
As for closing all of the vents but the
powered vents, the powered vents will have to draw air from somewhere. The
air will be coming from inside the living area, as well as cracks and
crevices around the foundation walls. Crawlspaces are not airtight. The air
will still be entering. The problem would come in when the powered vents
stopped running in that scenario. There would be no place for the moisture
to exit.
Return
to Humidistats
|